CIRCUIT BREAKERS
PUSH BUTTON CIRCUIT BREAKER
B7000 Series PUSH BUTTON THERMAL CIRCUIT BREAKER
“B7000” Series breakers are UL 1077 recognized as Supplementary protectors, File E99607, and CSA Certified as appliance Components pro-
tectors, File LR62590.
B7000 Series are single pole, thermal circuit breakers that feature a recessed reset button which cannot be manually pulled out to disconnect
the circuit. When an overload occurs and the breaker opens, it allows the reset button to “pop out” for visible trip indication.
No. B7000
- Clear
plastic boot for Philmore
No. B7000 - Series
Push Button circuit
breaker. Protects reset
button from dust and
moisture.
Endurance: 1,000 times at least
Calibration: Breaker will continuously carry 100% of rated load.
It may trip between 101% and 144% of rated load, but must
trip at 145% at 25º C.
Dielectric Strength: Over 1,500 volts RMS.
Max. Operating Voltages: 50VDC, 250VAC
Interrupt Capacity: 2,000 Amps, at 50 VDC(1-30 amp Models)
1,000 Amps, at 250VAC (1-30 amp Models)
Approvals
*
Approval: 3 -30 A 125/250 VAC
c
*
Approval: 5A, 10A, 15A, 20A125 VAC
Part No. Amps.
Maximum
Resistance in
ohms
Trip time@
200% of Rating
B7003
3
.18
10-45 Seconds
B7004
4
0.10
10-45 Seconds
B7005
5
.026
10-45 Seconds
B7006
6
0.15
10-45 Seconds
B7007
7
.020
10-45 Seconds
B7008
8
.020
10-45 Seconds
B7010
10
.014
6 to 30 Seconds
B7012
12
.010
6 to 30 Seconds
B7015
15
.010
6 to 30 Seconds
B7020
20
.006
6 to 30 Seconds
B7025
25
0.005
6 to 30 Seconds
B7030
30
.004
6 to 30 Seconds
B7035
35
.004
6 to 30 Seconds
B7040
40
.004
6 to 30 Seconds
B7045
45
.002
6 to 30 Seconds
B7050
50
.002
6 to 30 Seconds
B7060
60*
0.002
Within 60 Seconds
B7070
70*
0.0015
Within 60 Seconds
B7080
80*
0.0015
Within 60 Seconds
B7090
90*
0.001
Within 60 Seconds
Derating Factor
TEMP 50A - 100A
60°C x 0.50 ohm
55°C x 0.55 ohm
50°C x 0.60 ohm
45°C x 0.65 ohm
40°C x 0.72 ohm
35°C x 0.80 ohm
30°C x 0.85 ohm
25°C x 1.00 ohm
20°C x 1.10 ohm
15°C x 1.15 ohm
10°C x 1.25 ohm
(For Reference Only)
Specifications:
* Input Power:
125 VAC / 250 VAC / 50 VDC.
* Dielectric Strength:
1500 VAC / 1 minute.
* Interrupt Capacity:
125 VAC x 1000 A,
250 VAC x 2000 A.
* Insulation Resistance:
> 100 M
* Calibration:
25 C-100% of rated current-continuously carried.
25 C-between 101% to 145%-may trip or not.
25 C-150% of rated current- trip within 1 hour.
25 C-200% of rated current-trip within 1 minute.
* Contact Endurance:
125 VAC x 150% of rated current - 500 cycles
Screw Terminals
* = (60A - 90A)
(3A - 50A)